On-Line Electronics will be closed for the Holidays from Wednesday, December 24th, 2025 through Friday, January 2, 2026. There will be no shipping or receiving during this time. We will be open for business on Monday January 5, 2026. From our families to yours, HAPPY HOLIDAYS!
Underwriters Laboratories Inc., UL, E198726 Sec.1, UL 121201
UL International Netherlands B.V., UL, E175199 Sec.1, UL 508
National Radio Research Agency, KC, MSIP-REM-W43-SIM750
Det Norske Veritas, Germanischer Lloyd, DNV GL, TAA00000Y7
TUEV Nord Cert GmbH, IECEx, IECEx TUN 16.0046X, IEC 60079-0
American Bureau of Shipping, ABS, 18-HG1778162-PDA
CQST/CNEx, CCCEx, 2020312310000214, CNCA-C23-01
Specifications
Technical Data
Signal type: RS-232 || RS-422 / RS-485
Baud rate: 300 Baud … 115.2 kBd
Bit transfer: RS-485/-422: ISO 8482 / DIN 66259 - 4; RS-232: EIA/TIA-232-F
Transmission channels: 1 TxD / 1 RxD, full duplex, half duplex, 7- or 8-bit data, 1 or 2 stop bits
Line length: RS-485/-422: max. approx. 1000 m, RS-232: max. 40 m, data exchange mode/DMX: max. 100 m twisted-pair cable
Data width: 8, 24 or 48 bytes (parameterizable)
Number of data bits: 7/8, adjustable
Number of stop bits: 1/2, adjustable
Buffer: 2560 bytes for reception / 512 bytes for transmission
Supply voltage (system): 5 VDC; via data contacts
Power consumption (5 V system supply): 85 mA
Supply voltage (field): 24 VDC (-25 … +30 %); via power jumper contacts (power supply via blade contact; transmission via spring contact); Derating must be observed!
Rated surge voltage: 1 kV
Number of incoming power jumper contacts: 2
Number of outgoing power jumper contacts: 2
Current carrying capacity (power jumper contacts): 10 A
Derating: Derating (supply voltage): Surrounding air temperatures under laboratory conditions: (-25 … +30 %); for -40 … +55 °C: 24 V (-25 … +20 %); for +55 … +70 °C: 24 V (-25 … +10 %); Lower limit in all temperature ranges: −27.5 % (including 15 % residual ripple)
Connection Data
Connection technology: inputs/outputs: 8 x CAGE CLAMP®
Relative humidity (with condensation): Short-term condensation per Class 3K7/IEC EN 60721-3-3 and E-DIN 40046-721-3 (except for wind-driven precipitation, water and ice formation)
Vibration resistance: Per IEC 60068-2-6 (acceleration: 5g), EN 60870-2-2, IEC 60721-3-1, -3, EN 50155; EN 61373
Shock resistance: Per IEC 60068-2-27 (15g/11 ms/half-sine/1,000 shocks; 25g/6 ms/1,000 shocks), EN 50155, EN 61373
EMC immunity to interference: Per EN 61000-6-1, -2; EN 61131-2; marine applications; EN 50121-3-2; EN 50121-4, -5; EN 60255-26; EN 60870-2-1; EN 61850-3; IEC 61000-6-5; IEEE 1613; VDEW: 1994
EMC emission of interference: Per EN 61000-6-3, -4, EN 61131-2, EN 60255-26, marine applications, EN 60870-2-1, EN 61850-3, EN 50121-3-2, EN 50121-4, -5
Exposure to pollutants: Per IEC 60068-2-42 and IEC 60068-2-43
Permissible H2S contaminant concentration at a relative humidity 75 %: 10 ppm
Permissible SO2 contaminant concentration at a relative humidity 75 %: 25 ppm
Commercial Data
Packaging type: Box
Country of origin Sales Organisation Germany: DE
GTIN: 4050821460398
Customs tariff number Sales Organisation Germany: 85389099990