On-Line Electronics will be closed for the Holidays from Wednesday, December 24th, 2025 through Friday, January 2, 2026. There will be no shipping or receiving during this time. We will be open for business on Monday January 5, 2026. From our families to yours, HAPPY HOLIDAYS!
UL International Netherlands B.V., UL, E175199 Sec.1, UL 508
TUEV Nord Cert GmbH, TUEV Nord, TÜV 07 ATEX 554086 X en., EN 60079-0
Underwriters Laboratories Inc., UL, E198726 Sec.1, UL 121201
American Bureau of Shipping, ABS, 19-HG1821926
Det Norske Veritas, Germanischer Lloyd, DNV GL, TAA0000194
Nippon Kaiji Kyokai, NK, TA17255M
CQST/CNEx, CCCEx, 2020312310000215, CNCA-C23-01
TÜV Rheinland do Brasil Ltda., INMETRO, BR-Ex_TÜV 12.1297 X, IEC 60079
Specifications
Technical Data
Communication: Modbus® RTU
Visualization: Without
Programming languages per IEC 61131-3: Instruction List (IL) || Ladder Diagram (LD) || Function Block Diagram (FBD), Continuous Function Chart (CFC) || Structured Text (ST) || Sequential Function Chart (SFC)
Programming environment: WAGO-I/O-PRO V2.3 (based on CODESYS V2.3)
Cycle time: < 3 ms for 1000 bit instructions/ 256 digital I/O
Baud rate: 1.2 kBd … 115.2 kBd
Bus segment length (max.): 1200 m
Transmission medium (communication/fieldbus): Shielded Cu cable 2 (4) x 0.25 mm²
Number of fieldbus nodes on master (max.): 99
Number of I/O points: 6000
Program memory: 32 kByte
Data memory: 32 kByte
Non-volatile software memory: 8 kB
Memory for fieldbus input variables (max.): 512 Byte
Memory for fieldbus output variables (max.): 512 Byte
Number of modules per node (max.): 64
Input and output (fieldbus) process image (max.): 1024 Byte/1024 Byte
Supply voltage (system): 24 VDC (-25 … +30 %); via pluggable connector (CAGE CLAMP® connection)
Input current (typ.) at nominal load (24 V): 500 mA
Power supply efficiency (typ.) at nominal load (24 V): 87 %
Power consumption (5 V system supply): 350 mA
Total current (system supply): 1650 mA
Supply voltage (field): 24 VDC (-25 … +30 %); via power jumper contacts
Current carrying capacity (power jumper contacts): 10 A
Number of outgoing power jumper contacts: 3
Isolation: 500 V system/supply
Connection Data
Connection technology: communication/fieldbus: Modbus RTU: 1 x D-sub 9 socket
Connection technology: system supply: 2 x CAGE CLAMP®
Connection technology: field supply: 6 x CAGE CLAMP®