Online Electronics

WAGO 2010-1202

2010-1202 WAGO 2010-1202

WAGO 2010-1202
Part # 2010-1202
Manufacturer WAGO
GTIN 4017332076111
Condition New
Price: $ 3.82

Please Contact Us for Stock Availability

Qty
Note: you must order at least 10 items
Order by 3PM MST (subject to stock availability) same day shipping available!
2 CONDUCTOR RL MTD TERM BLK-TJS
Got questions? Send us a message or call us at 1-800-335-5111 for additional assistance.
2-Conductor through terminal block suitable for Ex e applications

Features

Approvals

  • Physikalisch Technische Bundesanstalt (PTB), ATEx, PTB 05 ATEX 1070 UII 2 G Ex eb II C bzw. I M 2 Ex eb I Mb, EN 60079
  • DEKRA Certification B.V., KEMA/KEUR, 71-119201, EN 60947
  • CQST/CNEx, CCCEx, 2020312313000161, CNCA-C23-01
  • UL International Germany GmbH, UL, E45172, UL 1059
  • DEKRA Certification B.V., CSA, 70111238, C22.2 No. 158
  • DEKRA Certification B.V., CCA, NTR NL 7876, EN 60947
  • UL International Germany GmbH c/o Physikalisch Technische Bundesanstalt, AEx, E185892, UL 60079
  • Brjansker Zertifizierungsstelle, EAC, RU C-DE.AM02.B.00127/19, TP TC 012/2011
  • Physikalisch Technische Bundesanstalt (PTB), IECEx, IECEx PTB 06.0003 U Ex eb IIC Gb and Ex ebI Mb, IEC 60079
  • American Bureau of Shipping, ABS, 20-HG1941090-PDA
  • Lloyds Register, LR, 91/20112 (E9), EN 60947
  • Det Norske Veritas, Germanischer Lloyd, DNV GL, TAE00001V2
  • Bureau Veritas S.A., BV, 38586/A0 BV, EN 60947

Specifications

Ratings Per Iec/En

  • Ratings per: IEC/EN 60947-7-1
  • Nominal voltage (III/3): 800 V
  • Rated surge voltage (III/3): 8 kV
  • Rated current: 57 A
  • Rated current 2: 76 A
  • Legend (ratings): (III / 3) ≙ Overvoltage category III / Pollution degree 3

Ratings Per Ul

  • Approvals per: UL 1059
  • Rated voltage UL (Use Group B): 600 V
  • Rated current UL (Use Group B): 65 A
  • Rated voltage UL (Use Group C): 600 V
  • Rated current UL (Use Group C): 65 A

Ratings Per Csa

  • Rated voltage CSA (Use Group B): 600 V
  • Rated current CSA (Use Group B): 65 A
  • Rated voltage CSA (Use Group C): 600 V
  • Rated current CSA (Use Group C): 65 A

Ex Information

  • Ratings per: ATEX: PTB 05 ATEX 1070 U / IECEx: PTB 06.0003U (Ex eb IIC Gb)
  • Rated voltage EN (Ex e II): 550 V
  • Rated current (Ex e II): 51 A

Connection 1

  • Connection technology: Push-in CAGE CLAMP®
  • Actuation type: Push-in || Operating tool
  • Connectable conductor materials: Copper
  • Nominal cross-section: 10 mm²
  • Solid conductor: 0.5 … 16 mm² / 20 … 6 AWG
  • Solid conductor; push-in termination: 4 … 16 mm² / 14 … 6 AWG
  • Fine-stranded conductor: 0.5 … 16 mm² / 20 … 6 AWG
  • Fine-stranded conductor; with insulated ferrule: 0.5 … 10 mm² / 20 … 8 AWG
  • Fine-stranded conductor; with ferrule; push-in termination: 4 … 10 mm² / 12 … 8 AWG
  • Note (conductor cross-section): Depending on the conductor characteristic, a conductor with a smaller cross-section can also be inserted via push-in termination.
  • Strip length: 17 … 19 mm / 0.67 … 0.75 inch
  • Wiring direction: Front-entry wiring

Physical Data

  • Width: 10 mm / 0.394 inch
  • Height: 67.8 mm / 2.669 inch
  • Depth from upper edge of DIN-rail: 36.9 mm / 1.453 inch

Mechanical Data

  • Design: Horizontal type
  • Mounting type: DIN-35 rail
  • Marking level: Center/side marking

Material Data

  • Color: Orange
  • Insulation material: Polyamide (PA66)
  • Flammability class per UL94: V0
  • Fire load: 0.293 MJ
  • Weight: 17.246 g

Commercial Data

  • Packaging type: Box
  • Country of origin Sales Organisation Germany: DE
  • GTIN: 4017332076111
  • Customs tariff number Sales Organisation Germany: 85369010000
: *
: *
: *
 
 

Copyright © 2004- by On-Line Electronics, Inc., All Rights Reserved - Developed by EngNet - Shipping & Returns  |  Terms & Conditions  |  Privacy Policy