Bureau Veritas S.A., BV, 40179_B0, Rules for class. of Steel Ships
UL International Netherlands B.V., UL, E175199 Sec.4, UL 508
Polski Rejestr Statków, PRS, TE/2186/880590/18
Det Norske Veritas, Germanischer Lloyd, DNV GL, TAA00001D1
DEKRA EXAM GmbH, ATEX, BVS_14_ATEX_E_091_X, EN 60079-0
Specifications
Notes
Note: Optocouplers and solid state relays are designed for use in signal processing networks, which are not supplied by the low-voltage power supply networks.
Control Circuit
Nominal input voltage UN: DC 24 V
Input voltage range (low level): DC 0 … 10 V
Input voltage range (high level): DC 18.8 … 31.2 V
Nominal input current at UN: 9.2 mA
Load Circuit
Circuit type: 2-wire connection
Limiting continuous current: 3 A
Inrush current (resistive) (max.): (AC) 15 A / 0.01 s